UL 2225:2019-05 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations.
1.1 These requirements cover Type MC-HL metal-clad cable for use in hazardous (classified) locations,
Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class I, Zone 1,
Groups IlA, lIB, and lIC; and Zone 20, 21, and 22 in accordance with the National Electrical Code, NFPA 70.
1.2 These requirements cover Type ITC-HL instrumentation tray cable for use in hazardous (classified)
locations, Class I, Division 1, Groups A, B, C, and D, and Class I, Zone 1, Groups llA, lIB, and IIC; and
Zone 20, 21, and 22 in accordance with the National Electrical Code, NFPA 70.
1.3 These requirements cover Type TC-ER-HL tray cable for use in hazardous (classified) locations, Class I, Zone 1, Groups IIA, IIB, and IIC in accordance with the National Electrical Code, NFPA 70.
1.4 These requirements cover explosionproof and dust-ignition proof cable sealing fittings for use in
hazardous (classified) locations, Class I, Division 1 and 2, Groups A, B, C, and D; Class II, Division 1 and
2, Groups E, F, and G in accordance with the National Electrical Code, NFPA 70.
1.5 These requirements cover explosionproof and dust-ignitionproof cable sealing fittings intended for use on mobile offshore oil rigs and drilling platforms, and other marine vessels. Investigations of these fittings include an evaluation for conformity to the installation and use provisions of Title 46 Code of Federal Regulations Sub-part 111.105 and Subpart 111.60 of the United States Coast Guard Electrical Engineering Regulations, Subchapter J (Parts 110 to 113 inclusive) as applied by the authority having jurisdiction.
1.6 These requirements cover increased safety “e” cable fittings and flameproof “d” cable sealing fittings for use in Class I, Zone 1 Groups IlA, lIB and lIC hazardous (classified) locations, in accordance with the National Electrical Code, NFPA 70.
1.7 These requirements cover increased safety “e” cable fittings and flameproof “d” cable sealing fittings
for use in hazardous (classified) locations, Class I, Zone 1 for use on mobile offshore oil rigs and drilling
platforms, and other marine vessels. Investigations of these fittings include an evaluation for conformity to
the installation and use provisions of Title 46 Code of Federal Regulations Sub-part 111.105 and Subpart
111.60 of the United States Coast Guard Electrical Engineering Regulations, Subchapter J (Parts 110 to
113 inclusive) as applied by the authority having jurisdiction.
1.8 These requirements cover increased safety “e” cord connectors and flameproof “d” cord connectors for use only with extra-hard usage cord in hazardous (classified) locations, Class I, Zone 1 in accordance with the National Electrical Code, NFPA 70.
1.9 These requirements cover dust ignition protection by enclosure “t” and “tD” cable fittings for use in Zone 20, 21, and 22 hazardous (classified) locations in accordance with the National Electrical Code, NFPA 70.UL 2225 pdf download.