AS NZS 60092.354:2020 Electrical installations in ships Part 354: Single- and three-core power cables with extruded solid insulation for rated voltages 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV) (IEC 60092- 354:2014 (ED.3.0) MOD).
This part of IEC 60092 is applicable to shipboard and offshore power cables with extruded solid insulation, conductor and core screening, having a voltage rating of one of the following:
3,6/6 (7,2) kV, 6/10 (12) kV, 8,7/15 (17,5) kV, 12/20 (24) kV, 18/30 (36) kV.
NOTE 1 Subclause 4.1 gives more details.
The cables are intended for fixed installations.
The various types of power cables are given in 5.1. The constructional requirements and test methods are aligned with those indicated in IEC 60092-350, unless otherwise specified in this standard.
The object of this standard is:
— to standardize cables whose safety and reliability are ensured when they are installed in accordance with the requirements of IEC 60092-352 or IEC 61892-4;
— to lay down standard manufacturing requirements and characteristics of such cables directly or indirectly bearing on safety;
— to specify test methods for checking conformity with those requirements.
NOTE 2 Only radial field cables are covered.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60038, IEC standard voltages
IEC 60092-350:2014, Electrical installations in ships — Part 350: General construction and test methods of power, control and instrumentation cables for shipboard and offshore applications
IEC 60092-360, Electrical installations in ships — Part 360: Insulating and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunication cables
IEC 60228, Conductors of insulated cables
IEC 60332-1-2, Tests on electric and optical fibre cables under fire conditions — Part 1-2:
Test for vertical flame propagation for a single insulated wire or cable — Procedure for 1 kW pre-mixed flame
4.2 Markings
4.2.1 Indication of origin and voltage identification
Cables shall comply with 4.1.3 of IEC 60092-350:2014 with respect to:
a) indication of origin;
b) rated voltage and cable construction (number of cores and cross-sectional area of the construction).AS NZS 60092.354 pdf download.